Wind Load Calculator

Calculate design wind pressures per ASCE 7-22 directional procedure (Chapter 27). Velocity pressure qh, gust factor G, and pressure coefficients Cp for windward wall, leeward wall, sidewalls, and roof.

ASCE 7-22 ยท US standard ยท results shown in both psf and kPa

Site & Wind Speed

mph
144.8 km/h
ft
9.1 m
1.0 = flat, up to 1.5 for hilltop

Building Parameters

II โ€” Iw = 1
0.85 for buildings (ASCE 7)
0.85 for rigid buildings (f > 1 Hz)
ยฐ
Affects Cp roof
0.18 enclosed, 0.55 partial

Wind Pressure Results

Kh = 0.98qh = 17.273 psf (827 Pa)Iw = 1
Windward wall (Cp = +0.8)
+9.1 psf+0.436 kPa
Leeward wall (Cp = โˆ’0.5)
-4.7 psf-0.225 kPa
Side walls (Cp = โˆ’0.7)
-7.63 psf-0.365 kPa
Roof windward (slope 10ยฐ, Cp = -0.7)
-7.63 psf-0.365 kPa

Positive (+) = pressure toward surface (inward). Negative (โˆ’) = suction away from surface (outward). All values are net (external โˆ’ internal). Leeward and sidewall/roof suctions act simultaneously with windward pressure โ€” combine for lateral load.

Engineering Reference

ASCE 7-22 Velocity Pressure Equation

qz = 0.00256 ร— Kz ร— Kzt ร— Kd ร— Vยฒ (psf, V in mph)
qz = 0.613 ร— Kz ร— Kzt ร— Kd ร— Vยฒ (Pa, V in m/s)

Design pressure: p = qh ร— G ร— Cp โˆ’ qi ร— (ยฑGCpi)

The basic wind speed V is the 3-second gust speed at 33 ft (10 m) above ground in open terrain with 700-year mean recurrence interval (Risk Category II). ASCE 7-22 replaced the earlier 50-year MRI maps โ€” wind speeds are higher but importance factors for standard occupancy are 1.0.

Exposure Categories

Exposure B: Surface roughness B โ€” urban/suburban areas, wooded areas, or terrain with closely spaced obstructions the size of single-family dwellings or larger
Exposure C: Open terrain with scattered obstructions having heights generally less than 30 ft (9.1 m); flat open country and grasslands; all cases between exposures B and D
Exposure D: Flat, unobstructed areas exposed to wind flowing over open water for a distance of at least 1 mile (1.6 km); coastal hurricane zones

Note: Exposure A (large city centres) was removed in ASCE 7-02. There is no Exposure A in ASCE 7-10 onwards. For dense urban environments, use Exposure B with reduced Kz values from Table 26.6-1.

Worked Example โ€” 90 mph, 30 ft, Exposure C

V = 90 mph, h = 30 ft, Exposure C, Risk Cat II (Iw = 1.0)
Kh (Table 26.6-1, Exp C, 30 ft) = 0.98
Kzt = 1.0 (flat), Kd = 0.85, G = 0.85

qh = 0.00256 ร— 0.98 ร— 1.0 ร— 0.85 ร— 90ยฒ = 17.3 psf (828 Pa)

Windward wall (Cp=0.8, Cpi=0.18):
p = 17.3 ร— 0.85 ร— 0.8 โˆ’ 17.3 ร— 0.85 ร— 0.18 = 11.75 โˆ’ 2.64 = +9.1 psf (+0.44 kPa)

Leeward wall (Cp=โˆ’0.5):
p = 17.3 ร— 0.85 ร— (โˆ’0.5) โˆ’ 17.3 ร— 0.85 ร— (โˆ’0.18) = โˆ’7.35 + 2.64 = โˆ’4.7 psf (โˆ’0.22 kPa)

How Wind Loads Are Transferred Through a Structure

Wind pressure acts on the building envelope โ€” walls, roof, and cladding โ€” and must be transferred through the structural system to the foundations. The load path is: cladding panels โ†’ girts and purlins (secondary members) โ†’ columns and rafters (primary frames) โ†’ bracing and shear walls โ†’ foundation. Each element must be designed for the tributary wind load it attracts.

Roof uplift is often the governing load for low-rise buildings. The combination of positive windward wall pressure pushing inward and negative (suction) roof pressure pulling upward can exceed gravity loads in high-wind regions. Connections between roof diaphragm, wall top plates, and columns must be designed as continuous load paths โ€” this is the primary cause of roof failures in hurricanes when straps or anchors are undersized.

Components and Cladding vs. Main Wind Force Resisting System

ASCE 7 distinguishes two load cases. The Main Wind Force Resisting System (MWFRS) is the structural assembly that resists the overall lateral force and overturning moment โ€” typically moment frames, braced frames, or shear walls. MWFRS pressures use the GยทCp method with external Cp values from ASCE 7 Figure 27.3-1.

Components and Cladding (C&C) covers individual elements: windows, cladding panels, fasteners, purlins, and girts. C&C pressures are generally higher than MWFRS pressures because small tributary areas experience higher local suctions, particularly at building corners, eave edges, and ridge lines. Always check both C&C and MWFRS โ€” the governing case differs by element type.

Common Mistakes in Wind Load Calculations

  • Wrong wind speed map: ASCE 7-10 and later editions use ultimate (LRFD) wind speeds. Earlier editions (ASCE 7-05) used allowable stress design speeds. Mixing editions produces unconservative results.
  • Flat terrain assumption: If the site has hills, ridges, or escarpments within 2 miles, the topographic factor Kzt may increase design pressure by 10โ€“40%.
  • Ignoring internal pressure: Open or partially enclosed buildings see large internal pressure coefficients (GCpi = ยฑ0.55). Failing to add internal pressure to external suction understates net uplift on roofs.
  • Single design pressure for all cladding: Corner zones have substantially higher C&C pressures than field zones. Apply zonal pressures to the corresponding tributary areas.

Disclaimer

Wind load calculations are complex and jurisdiction-dependent. This calculator implements simplified ASCE 7 procedures and is intended for preliminary estimation and educational purposes only. Structural design must be performed by a licensed structural engineer in accordance with the applicable building code for the project location.


Also in Engineering