Boiler & Hydronic Sizing Calculator
Size a boiler for a given heat load, calculate design flow rate, pipe velocity, expansion tank, and radiator output correction per ASHRAE / CIBSE / EN 442.
ASHRAE / CIBSE / EN 442 · SI unitsHeat Load & Design Conditions
Boiler & Fluid
Pipe Velocity Check
Expansion Tank
Radiator Output Correction (EN 442)
Boiler Sizing Results
Pipe Velocity
Expansion Tank
Closed diaphragm tank — pre-charge to system cold-fill pressure (typically 0.5–1.0 bar). Add 10–15% for safety.
Radiator Output (EN 442 Correction)
Output is 0% below the EN 442 rating. Low-temperature systems typically need 20–40% larger radiators than the catalogue value.
Engineering Reference
Hydronic Flow Rate — ASHRAE
The fundamental hydronic sizing equation (ASHRAE HVAC Systems & Equipment, Ch. 12):
Where Q̇ is heat transfer rate (kW), ρ is fluid density (kg/m³), Cp is specific heat (kJ/(kg·K)), and ΔT is the temperature differential. Lower ΔT systems (underfloor heating at ΔT 5–11°C) require much higher flow rates for the same heat output — size pumps and pipes accordingly.
Radiator Derating — EN 442
EN 442 rates radiators at ΔT50K standard conditions: mean water 70°C (flow 75 / return 65), room 20°C. LMTD is used, not arithmetic mean.
Output = Rated × (ΔT_actual / ΔT_rated)^1.3
The exponent 1.3 is from EN 442 — it accounts for mixed convection/radiation. At flow 55°C / return 45°C / room 20°C, the LMTD ≈ 27.5K (vs rated 50K), so correction factor = (27.5/50)^1.3 ≈ 0.49 — the radiator only delivers ~49% of its catalogue output. Sizing for heat pump low-temperature systems typically requires 2× the radiator area.
Expansion Tank — ASHRAE Fundamentals §13.4
Closed (diaphragm/bladder) expansion tanks must accommodate the thermal expansion of the entire system volume as water heats from cold-fill to operating temperature:
Pre-charge the tank to the system cold-fill pressure (typically 0.5–1.5 bar gauge). Add 10–15% to the calculated volume. Under-sized tanks result in pressure relief valve lift on every heating cycle.
Worked Example — 80 kW System, ΔT 20°C
Condensing gas η = 0.94 → Input = 92 / 0.94 = 97.9 kW
Flow rate: V̇ = 92 / (972 × 4.196 × 20) = 0.00113 m³/s = 1.13 L/s = 67.7 L/min
28 mm pipe (ID 26.2 mm): v = 0.00113 / (π × 0.0131²) = 2.1 m/s — elevated, try 35 mm
35 mm pipe (ID 33.2 mm): v = 0.00113 / (π × 0.0166²) = 1.3 m/s — acceptable
Expansion tank (system 200 L, cold 10°C, hot 80°C, 3 bar):
ρ_cold = 999.8 kg/m³, ρ_hot = 971.8 kg/m³
Expansion fraction = 999.8/971.8 − 1 = 0.0288 (2.88%)
Acceptance = 1 − 1.013/3 = 0.662
V_tank = 200 × 0.0288 / 0.662 = 8.7 L → specify 10 L tank
Also in Engineering
- → Chilled Water/Brine Flow — Flow rate vs delta-T and cooling capacity calculations
- → ASHRAE Humidity Calculator — Calculate dew point and verify conditions against ASHRAE TC 9.9 environmental classes
- → Cooling Load Calculator — Calculate cooling load (BTU/hr or kW) for buildings, rooms, equipment
- → Pipe Flow Velocity — Calculate flow velocity in pipes based on flow rate and pipe diameter